166
Rockwell Automation Publication 20Y-UM001F-EN-P - April 2017
Appendix C
Application Notes
Advanced Procedure to Size the AFE
1. Convert all motor powers to kW (kW = Hp x 0.746).
2. Determine the total power and input current required during
acceleration.
(1)
For Motoring Loads: P
Drive
= P
Motor
/ Motor Efficiency
For Regenerating Loads: P
Drive
= P
Motor
* Motor Efficiency
P
Accel
= P
Drive1
+ P
Drive2
+ …
Calculate the input current required on the regenerative unit during
acceleration, taking advantage of the 110% for 1 minute overload rating
of the regenerative unit.
I
Input
= P
Accel
x 1000 / (√ 3 x V
LL
x 1.1),
where P
Accel
is in kW, and V
LL
= RMS line-to-line AC input voltage.
3. Determine the total power and input current required during steady-
state run operation.
For Motoring Loads: P
Drive
= P
Motor
/ Motor Efficiency
For Regenerating Loads: P
Drive
= P
Motor
* Motor Efficiency
P
Run
= P
Drive1
+ P
Drive2
+ …
Calculate the steady-state input current required on the regenerative
unit.
I
Input
= P
Run
x 1000 / (√ 3 x V
LL
),
where P
Run
is in kW, and V
LL
= RMS line-to-line AC input voltage.
4. Determine the total power and input current required during
deceleration.
For Motoring Loads: P
Drive
= P
Motor
/ Motor Efficiency
For Regenerating Loads: P
Drive
= P
Motor
* Motor Efficiency
P
Decel
= P
Drive1
+ P
Drive2
+ …
Calculate the input current required on the regenerative unit during
deceleration, taking advantage of the 110% for 1 minute overload rating
of the regenerative unit.
I
Input
= P
Decel
x1000 / (√ 3 x V
LL
x 1.1),
where P
Decel
is in kW, and V
LL
= RMS line-to-line AC input voltage.
5. Compare the absolute values of the input current required for the
regenerative unit during acceleration, deceleration, and steady state.
6. Select the regenerative unit with the input current rating that meets or
exceeds the worst case input current.
(1) P
Motor
is the motor power required for the application. The P
Motor
could be positive if that section of the machine is motoring, or
negative if that section of the machine is regenerating.
Summary of Contents for Allen-Bradley PowerFlex 700AFE
Page 8: ...8 Rockwell Automation Publication 20Y UM001F EN P April 2017 Table of Contents Notes ...
Page 164: ...164 Rockwell Automation Publication 20Y UM001F EN P April 2017 Appendix B HIM Overview Notes ...
Page 184: ...184 Rockwell Automation Publication 20Y UM001F EN P April 2017 Index Notes ...
Page 185: ......