94
Rockwell Automation Publication 20Y-UM001F-EN-P - April 2017
Chapter 3
Startup
To stop the AFE, turn the 0-1-START switch to 0 (off ).
IMPORTANT
Pressing the
(Stop) key on the HIM only stops the AFE
output – it does not open the MCCB to stop the AFE.
When a voltage drop or a blackout occurs in the supplying network,
the undervoltage release coil opens the circuit breaker. When the
supply is restored, the precharging and MCCB closing must be
reinitiated. To turn on the AFE, turn the 0-1-START switch to START
and let it automatically return to 1 (on).