92
Rockwell Automation Publication 20Y-UM001F-EN-P - April 2017
Chapter 3
Startup
Status Indicators
For information on AFE status indicators, see
.
Control Devices
shows the operators or control devices (switches, push buttons, and
status indicators) on an IP21 Rittal enclosure.
Figure 43 - Control Devices for AFE in IP21 Rittal Enclosure
The AFE READY status indicator lights up when precharge is completed, the
MCCB is closed, AC power is connected to the AFE, and no faults are active.
The AFE READY status indicator operates independent of the control
method.
The MCCB FAULT status indicator lights to indicate that the circuit breakers
are in a tripped state.
In an overcurrent situation, the fault that caused the circuit breaker to trip must
be identified and fixed before resetting the circuit breakers. The MCCB can be
reset only by pressing the MCCB RESET push button when the MCCB
CONTROL switch is in MAN.
MCCB (Motor-controlled Circuit Breaker) and Modes of Operation
There are three different modes in which the MCCB and precharge can be
controlled. The desired control is selected with the MCCB CONTROL
selector switch.
1.
AUTO
– Automatic operation that automatically precharges and closes
the MCCB when the supply voltage is energized.
a. Set the MCCB CONTROL switch to AUTO.
b. Set the 0-1-START switch to 1 (on).
AFE READY
MCCB CONTROL
(REM — MAN — AUTO)
0 — 1 — START
MCCB FAULT
MCCB RESET
0
1
MAN
AUTO
REM
START
Summary of Contents for Allen-Bradley PowerFlex 700AFE
Page 8: ...8 Rockwell Automation Publication 20Y UM001F EN P April 2017 Table of Contents Notes ...
Page 164: ...164 Rockwell Automation Publication 20Y UM001F EN P April 2017 Appendix B HIM Overview Notes ...
Page 184: ...184 Rockwell Automation Publication 20Y UM001F EN P April 2017 Index Notes ...
Page 185: ......