44
Rockwell Automation Publication 20Y-UM001F-EN-P - April 2017
Chapter 1
AFE in IP20 2500 MCC Style Enclosure – Installation/Wiring
Table 7 - Door Control Box I/O Terminal Designations for AFE in IP20 2500 MCC Style Enclosure
No.
Signal
Default
Configuration
Description
1
Analog In 1 (–)
(1)
(1)
Important:
Input must be configured with a jumper. AFE damage can occur if jumper is not installed properly. See
.
(2)
(2) These inputs/outputs are dependent on a number of parameters.
Isolated
(3)
, bipolar, differential,
9-bit and sign, 88k Ω input impedance.
A jumper (see
) selects 0…10V,
±10V, or 4…20 mA.
Default: 0…10V (Ri = 200k Ω),
4…20 mA (Ri = 100 ohm).
(3) Differential Isolation - External source must be maintained at less than 160V regarding PE. Input provides high common mode
immunity.
2
Analog In 1 (+)
3
Analog In 2 (–)
4
Analog In 2 (+)
5
–10V Pot Reference
—
2k Ω min, 10 mA max load, 1% accuracy
6
Pot Common (GND)
For (+) and (–) 10V pot references
7
+10V Pot Reference
—
2k Ω min, 10 mA max load, 1% accuracy
8
Analog Out 1 (+)
Bipolar (current out is not bipolar),
9-bit and sign, 2k Ω min load.
A jumper (see
) selects 0…10V,
±10V, or 4…20 mA.
9
Analog Out Common
10
Analog Out 2 (+)
11
Digital In 1
RunCmd
24V DC - Opto isolated (250V)
Low state: less than 5V DC
High state: greater than 20V DC, 11.2
mA DC
Enable: digital input 6 is jumper
selectable for HW Enable.
On-time: < 16.7 ms, Off-Time < 1 ms
12
Digital In 2
Ext. Reset
13
Digital In 3
Enable Mcont
14
Digital In 4
Contactor Ack
15
Digital In 5
LCL Temp
16
Digital In 6/Hardware
Enable, see
17
18
Digital In Common
Allows source or sink operation
19
+24V DC
(4)
(4) 150 mA maximum load. Can be used to provide control power from an external 24V source when main power is not applied.
—
Unit supplied logic input power
20
24V Common
—
Common for internal power supply
21
Digital Out 1 – N.C.
(5)
(5) Contacts in unpowered state. Any relay that is programmed as Fault or Alarm energizes (pick up) when power is applied to the
AFE, and de-energizes (drop out) when a fault or alarm exists. Relays selected for other functions energize only when that
condition exists and de-energizes when the condition is removed.
Contact Ctrl
Max Resistive Load:
240V AC/30V DC – 1200VA, 150 W
Max current: 5 A, Min Load: 10 mA
Max. Inductive Load:
240V AC/30V DC – 840VA, 105 W
Max current: 3.5 A, Min Load: 10 mA
IMPORTANT:
See the Attention above
this table for more details.
22
Digital Out 1 Common
23
Digital Out 1 – N.O.
24
Digital Out 2 – N.C.
Fault
25
Digital Out 2/3 Com.
26
Digital Out 3 – N.O.
(6)
(6) These sizes are not recommendationsWhen this output is configured as active, it can be wired to the Enable input of the
connected drives to prevent the AFE from supplying power when the AFE is not running.
Active
1
10
20
21
26
Summary of Contents for Allen-Bradley PowerFlex 700AFE
Page 8: ...8 Rockwell Automation Publication 20Y UM001F EN P April 2017 Table of Contents Notes ...
Page 164: ...164 Rockwell Automation Publication 20Y UM001F EN P April 2017 Appendix B HIM Overview Notes ...
Page 184: ...184 Rockwell Automation Publication 20Y UM001F EN P April 2017 Index Notes ...
Page 185: ......