Rockwell Automation Publication 20Y-UM001F-EN-P - April 2017
167
Application Notes
Appendix C
Voltage Boost
AFE parameter 61 [DC Volt Ref ] can be adjusted to boost the DC voltage.
The maximum value of parameter 61 [DC Volt Ref ] is:
[Rated Volts] x 1.35 x 1.3 for 400/480V units
[Rated Volts] x 1.35 x 1.15 for 600/690V units,
where [Rated Volts] is the AC input voltage for the AFE.
Th
e maximum AC output to the motor = [DC Volt Ref ] / (√ 2 x 1.1)
Example:
AC line voltage = 400V AC
Motor = 460V AC
Max [DC Volt Ref ] = 400 x 1.35 x 1.3 = 702V DC
Maximum AC output to motor = 702V DC / (√ 2 x 1.1) = 451V AC
In addition, the AC input current required by the AFE increases when using
voltage boost. The continuous and overload AC input current ratings must not
be exceeded, or the AFE trips on overload. See the
for sizing guidelines.
ATTENTION:
The AFE can be used for voltage boost but cannot be used to
lower the DC bus voltage. The minimum DC bus voltage is limited by the
rectified diode bridge voltage.