46
Rockwell Automation Publication 20Y-UM001F-EN-P - April 2017
Chapter 1
AFE in IP20 2500 MCC Style Enclosure – Installation/Wiring
Analog I/O Configuration
Table 8 - I/O Configuration for AFE in IP20 2500 MCC Style Enclosure
Hardware Enable Circuitry
You can program a digital input as an Enable input. The AFE software
interprets the status of this input. If the application requires the AFE to be
disabled without software interpretation, a dedicated hardware enable
configuration can be used.
Remove jumper J5 (
Figure 22
) and wire the enable input to Digital In 6 (see
). Verify that [Digital In6 Sel], parameter 226, is set to ‘1’ (Enable).
Table 9 - Hardware Enable Configuration for AFE in IP20 2500 MCC Style Enclosure
IMPORTANT
Analog I/O must be configured through programming, and the jumpers
shown in
Figure 22
for jumper locations and
for I/O
jumper configurations.
Signal
Jumper
Setting
Analog
inputs
J1 (analog in 1)
J2 (analog in 2)
0…20 mA
0…10V
±10V
Analog
outputs
J3 (analog out 1)
J4 (analog out 2)
0…20 mA
0…10V
±10V
ATTENTION:
For the AFE in the IP20 2500 MCC Style enclosure, digital
inputs 1, 3, 4, and 5, and digital outputs 1 and 2, are wired at the factory
and programmed to operate from the controls on the front of the
enclosure. Do not change the wiring and programming for those digital
inputs and outputs, or it results in malfunction of the system.
Signal
Jumper
Setting
Hardware
Enable
J5
Hardware enable
Input programmable (no hardware enable)
C D
B
A
J1
J2
C D
B
A
C D
B
A
J1
J2
C D
B
A
C D
B
A
J1
J2
C D
B
A
C D
B
A
J3
J4
C D
B
A
C D
B
A
J3
J4
C D
B
A
C D
B
A
J3
J4
C D
B
A
B
A
J5
B
A
J5
Summary of Contents for Allen-Bradley PowerFlex 700AFE
Page 8: ...8 Rockwell Automation Publication 20Y UM001F EN P April 2017 Table of Contents Notes ...
Page 164: ...164 Rockwell Automation Publication 20Y UM001F EN P April 2017 Appendix B HIM Overview Notes ...
Page 184: ...184 Rockwell Automation Publication 20Y UM001F EN P April 2017 Index Notes ...
Page 185: ......