Rockwell Automation Publication 20Y-UM001F-EN-P - April 2017
53
AFE in IP21 Rittal Enclosure – Installation/Wiring
Chapter 2
Frame 13
shows a basic one-line diagram for an AFE Frame 13 in an IP21
Rittal enclosure. The main component sections consist of the following items:
• AC line switchgear consisting of the input disconnect (Q0) and MCCB
motor-controlled circuit breaker (Q1)
• LCL filter (L1)
• Precharge circuit
• AFE power structure (U1) with AFE control assembly
• DC fuses (F2.1…F2.6)
Figure 25 - Basic One-line Diagram for an AFE Frame 13 in IP21 Rittal Enclosure
L1
L2
L3
R6.1
R6.2
+
-
U2
V2
W2
C1
C2
C3
C4
C5
C6
U1
V1
W1
Q1
Q0
Q5
K6
F6
F2.1
F2.2
F2.3
F2.4
F2.5
F2.6
DC+
DC-
W
PE
PE
DC+
DC-
V
PE
DC+
DC-
U
PE
AC Line Switchgear
LCL Filter (L1)
AFE
Power Structure (U1)
DC
Fuses
Precharge Circuit
3-phase
AC Input
DC Bus
Output
PowerFlex
Active Front End System
Precharge
Fuses
Precharge
Contactor
Motor Protection
Relay