AFE in IP21 Rittal Enclosure – Installation/Wiring
Chapter 2
• When it is unavoidable to cross control and signal wires with power
wires, always cross power wires at a 90° angle.
Signal and Control Wire Types
Table 14 - Recommended Signal Wire for AFE in IP21 Rittal Enclosure
Table 15 - Recommended Control Wire for Digital I/O
Figure 39 - AFE I/O Terminal Blocks and Jumpers
IMPORTANT
I/O terminals that are labeled ‘(–)’ or ‘Common’
are not
referenced to earth
ground. They are designed to reduce common mode interference.
Grounding these terminals can cause signal noise.
ATTENTION:
Inputs must be configured with software and jumpers (see
Analog I/O Configuration on page 79
). If you configure an analog input for
0…20 mA operation and drive it from a voltage source, you can cause
component damage. Verify proper configuration before you apply input
signals.
ATTENTION:
It is important to disable the variable frequency drives that are
connected to the AFE output when the AFE is not active (not modulating).
Connect the 'Inverter Enable' output of the AFE to each variable frequency drive
enable input, or enable parameter 132 [Contact Off Cnfg] to force off the main
contactor if there is a fault. This action makes sure that once the AFE stops
modulating, there is no motoring current flowing through the AFE IGBT diodes.
Failure to disable the AFE output can result in component damage or a reduction
in product life.
When you enable parameter 132, see
for details. The AFE is shipped
with parameter 132 disabled. The disabled parameter does not stop or shut
down DC output when a fault occurs.
Signal Type
Wire Types
Description
Minimum
Insulation Rating
Analog I/O
Belden 8760/9460
(or equivalent)
0.5 mm2(22 AWG), twisted pair,
100% shield with drain
(1)
(1) If the wires are short and contained within an enclosure that has no sensitive circuits, the use of shielded wire is not necessary,
but is always recommended.
300V, 75…90 °C
(167…194 °F)
Belden 8770
(or equivalent)
0.5 mm
2
(22 AWG), 3-conductor,
shielded for remote pot only
EMC compliance
See
for details.
Type
Wire Types
Description
Minimum
Insulation Rating
Unshielded
Per US NEC or applicable national or local
code
—
300V, 60 °C
(140 °F)
Shielded
Multi-conductor shielded cable such as
Belden 8770(or equivalent)
0.5 mm
2
(22 AWG),
3-conductor, shielded
Summary of Contents for Allen-Bradley PowerFlex 700AFE
Page 8: ...8 Rockwell Automation Publication 20Y UM001F EN P April 2017 Table of Contents Notes ...
Page 164: ...164 Rockwell Automation Publication 20Y UM001F EN P April 2017 Appendix B HIM Overview Notes ...
Page 184: ...184 Rockwell Automation Publication 20Y UM001F EN P April 2017 Index Notes ...
Page 185: ......