Troubleshooting
Table 24 - Instability in the AC Line Input Current and DC Bus Voltage
Incorrect digital input programming.
None
Program [Digital Inx Sel] for correct
inputs (see
Run programming can be missing.
There is some other start inhibit.
Check status bits of
parameter 100 [Start
Inhibits].
Correct the source of the inhibit.
Causes
Indication
Corrective Action
AC line voltage more than 5% above
normal.
Instability in AC line current
and DC bus voltage.
Can trip on fault F7 ‘Overload’.
Increase parameter 060 [DC Volt Ref]
proportional to the percentage of the
AC line voltage above nominal.
Negative reactive I Ref on parameter
065 [Reactive I Ref] with a soft (high
impedance) AC line.
Instability in AC line current
and DC bus voltage.
Can trip an F7 overload.
Change parameter 065 [Reactive I
Ref] value to zero. Verify if the AFE is
running on a soft line per AC line
source considerations.
Causes
Indication
Corrective Action