88
Rockwell Automation Publication 20Y-UM001F-EN-P - April 2017
Chapter 3
Startup
Status Indicators
For information on AFE status indicators, see
.
Control Devices
shows the operators or control devices (switches, push buttons, and
status indicators) on an IP20 2500 MCC Style enclosure.
Figure 42 - Control Devices for AFE in IP20 2500 MCC Style Enclosure
The AFE READY status indicator lights up when precharge is completed, the
input contactor K1 is closed, AC power is connected to the AFE, and no faults
are active. The AFE READY status indicator operates independent of the
control method.
The AFE FAULT status indicator lights to indicate that the AFE is in a fault
state.
In an overcurrent situation, the fault that caused the input circuit breaker (Q0)
to trip must be identified and fixed before resetting the breaker.
Modes of Operation
There are three different modes in which the contactor and precharge can be
controlled. The desired control is selected with the REM-AUTO-MAN
selector switch.
1.
AUTO
– Automatic operation that precharges and closes the contactor
when the supply voltage is energized.
a. Set the REM-AUTO-MAN switch to AUTO.
b. Set the OFF-ON-START switch to ON.
AFE READY
(REM — MAN — AUTO)
OFF — ON — START
AFE FAULT
AFE RESET
OFF
ON
MAN
AUTO
REM
START
Summary of Contents for Allen-Bradley PowerFlex 700AFE
Page 8: ...8 Rockwell Automation Publication 20Y UM001F EN P April 2017 Table of Contents Notes ...
Page 164: ...164 Rockwell Automation Publication 20Y UM001F EN P April 2017 Appendix B HIM Overview Notes ...
Page 184: ...184 Rockwell Automation Publication 20Y UM001F EN P April 2017 Index Notes ...
Page 185: ......