AFE in IP21 Rittal Enclosure – Installation/Wiring
Chapter 2
Frame 13 Power Structure
The AFE Frame 13 power structure in the IP21 Rittal enclosure contains
common mode capacitors that must be removed
. These capacitors are on the
Phase V (center) module of the power structure.
To remove these capacitors from the AFE Frame 13 power structure, follow
these steps.
1. Locate the common mode capacitors on the Phase V module of the
Frame 13 power structure.
2. Remove the common mode capacitors.
a. Disconnect the two black wires.
Location of Common Mode
Capacitors on Phase V Module of
Frame 13 AFE Power Structure
Phase V Module of Frame 13
Power Structure