174
Rockwell Automation Publication 1734-UM013J-EN-P - July 2014
Appendix C
Specifications
1734‐IB8S Series B temperature versus aggregate current
per module ‐ derating for both horizontal and vertical
installations
Pulse width
525
μ
s
Pulse period
144 ms
Maximum field capacitance limit permitted per test
output
100 nF
Current, max (when used to control muting lamp)
25 mA (to avoid fault when used as a muted lamp output)
Current, min (when used to control muting lamp)
5 mA (at which fault indication is generated when used as
a muted lamp output)
Residual voltage, max
0.3 V
Output leakage current, max
0.1 mA
Short circuit protection
Yes
POINTBus
POINTBus current, max
110 mA
Power dissipation, max
(1)
3.0 W
Thermal dissipation, max
10.25 BTU/hr
Power dissipation, typical
(2)
2.25 W
Isolation Voltage
50 V (continuous), Basic Insulation Type between field
side and system.
No isolation between individual channels.
Type tested at 500V AC for 60 s.
Power bus, operating supply voltage
24V DC nom, Class 2
Power bus, operating voltage range
19.2…28.8V DC, Class 2
Power bus current (no load), max
25 mA
Attribute
1734-IB8S Series B
2.8 A
-20 °C
(-4 °F)
40 °C
(104 °F)
55 °C
(131 °F)
0.55 A
Summary of Contents for Allen-Bradley 1734-IB8S
Page 1: ...POINT Guard I O Safety Modules Catalog Numbers 1734 IB8S 1734 OB8S 1734 IE4S User Manual ...
Page 4: ...4 Rockwell Automation Publication 1734 UM013J EN P July 2014 Summary of Changes Notes ...
Page 10: ...10 Rockwell Automation Publication 1734 UM013J EN P July 2014 Table of Contents ...
Page 14: ...14 Rockwell Automation Publication 1734 UM013J EN P July 2014 Preface Notes ...
Page 186: ...186 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix D Safety Data Notes ...
Page 211: ......