Rockwell Automation Publication 1734-UM013J-EN-P - July 2014
71
Install the Module
Chapter 4
In the following two examples, the negative terminal of the sensor power supply
and that of the 1734 terminal base COMMON must be at the same potential.
Use of an external power supply limits diagnostics and increases susceptibility to
noise.
Guidelines for Wiring Safety Analog Inputs on page 65
Figure 41 - 4-wire Voltage or Tachometer Sensor (SIL 2) with External Power Supply
Figure 42 - 4-wire Current Sensor (SIL 2) with External Power Supply
IMPORTANT
You are responsible for making sure that the sensor is receiving appropriate
power. Safety sensors that are not properly powered may not deliver accurate
signals to the analog input module.
V0
DC
V1
V2
V3
I0
I1
I2
I3
COM
COM
COM
COM
S0
FE
S1
S2
S3
+
-
Signal Return and Common are at the same potential.
1734-TB Terminal Bases
Signal (V)
+24V
Cable Shield
Signal Return
4-wire
Sensor
See
and
for tachometer wiring detail.
V0
DC
V1
V2
V3
I0
I1
I2
I3
COM
COM
COM
COM
S0
FE
S1
S2
S3
+
-
Signal Return and Common are at the same potential.
1734-TB Terminal Bases
Signal (V)
+24V
Cable Shield
Signal Return
4-wire
Sensor
Summary of Contents for Allen-Bradley 1734-IB8S
Page 1: ...POINT Guard I O Safety Modules Catalog Numbers 1734 IB8S 1734 OB8S 1734 IE4S User Manual ...
Page 4: ...4 Rockwell Automation Publication 1734 UM013J EN P July 2014 Summary of Changes Notes ...
Page 10: ...10 Rockwell Automation Publication 1734 UM013J EN P July 2014 Table of Contents ...
Page 14: ...14 Rockwell Automation Publication 1734 UM013J EN P July 2014 Preface Notes ...
Page 186: ...186 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix D Safety Data Notes ...
Page 211: ......