Configure the Module for a SmartGuard Controller
Auto-addressing with a
1734-PDN Adapter
With sequential auto-addressing, the leftmost node address is configured and a
parameter is set in that module to automatically assign addresses to the nodes
residing to the right of the module. The leftmost node can be a
POINT Guard I/O module or a standard POINT I/O module.
Follow these steps to use the auto-address feature.
1.
Reset any modules that you are not sure are out-of-box.
2.
Attach the first module to the 1734-PDN adapter.
3.
Use the node commissioning tool to set the node address of this module.
4.
Attach the additional nodes to the right of the module used in
steps
and
.
5.
Perform the auto-address feature on the module used in steps
.
A. Set the address of the leftmost I/O module.
B. When you configure the leftmost module, set Sequential AutoAddress to
‘Sequential Address’.
The module sequences the rest of the
modules to its right in the group.