Rockwell Automation Publication 1734-UM013J-EN-P - July 2014
129
Configuring Safety Connections between a GuardLogix Controller and POINT Guard I/O Modules on a DeviceNet Network
Chapter 7
9.
Click OK.
10.
On the Safety Tab, uncheck the Configuration Signature checkbox.
11.
Click OK and OK again to add the module to the I/O Configuration tree.
Complete the Safety
Configuration
Follow these steps to copy the configuration signature and safety network
number from RSNetWorx for DeviceNet software to the generic profile you set
up in the Logix Designer application.
1.
In RSNetWorx for DeviceNet software, double-click the module.
2.
On the Safety tab, click Copy Signature.
3.
In the Logix Designer application, right-click the DEVICENET-
SAFETYMODULE and choose Properties.
4.
On the Safety tab, check the Configuration Signature checkbox.
IMPORTANT
If you are using the 1734-IE4S module with a GuardLogix system, use the
application program to evaluate any dual channel requirements as well as
determine any process alarms.