Rockwell Automation Publication 1734-UM013J-EN-P - July 2014
135
Configuring Safety Connections between a GuardLogix Controller and POINT Guard I/O Modules on a DeviceNet Network
Chapter 7
1.
Click Review in the Report column to launch the device’s HTML report
in your default browser.
2.
Click Review All to generate an HTML verification report for all of the
devices listed.
3.
Review and print the verification reports for your records.
Lock Safety Devices
1.
Choose which devices to safety-lock by checking the checkbox in the Lock
column for each device that is ready to be safety-locked.
2.
You must check the acknowledgement checkbox before the locking
process can continue.
3.
Click Next.
The wizard performs a final comparison of the configuration signature in
each safety device to its configuration signature in RSNetWorx for
DeviceNet software before locking the device.
TIP
If a device’s status is Verify FAILED, more information is provided in
the verification failure report.
IMPORTANT
You must review the device configurations and record the configuration
signatures prior to operating a safety application.
IMPORTANT
Before you lock your safety device configurations, you must perform all of the
verification steps required for your application.
Summary of Contents for Allen-Bradley 1734-IB8S
Page 1: ...POINT Guard I O Safety Modules Catalog Numbers 1734 IB8S 1734 OB8S 1734 IE4S User Manual ...
Page 4: ...4 Rockwell Automation Publication 1734 UM013J EN P July 2014 Summary of Changes Notes ...
Page 10: ...10 Rockwell Automation Publication 1734 UM013J EN P July 2014 Table of Contents ...
Page 14: ...14 Rockwell Automation Publication 1734 UM013J EN P July 2014 Preface Notes ...
Page 186: ...186 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix D Safety Data Notes ...
Page 211: ......