146
Rockwell Automation Publication 1734-UM013J-EN-P - July 2014
Chapter 8
Replacing POINT Guard I/O Modules
1.
Remove the old I/O module and install the new module.
2.
Right-click your POINT Guard I/O module and choose Properties.
3.
Click the Safety tab.
4.
Click Reset Ownership.
5.
Click OK.
6.
Follow your company-prescribed procedures to functionally test the
replaced I/O module and system and to authorize the system for use.
If
then
the module is in out-of-box condition
go to step
No action is needed for the GuardLogix controller to take
ownership of the module.
an SNN mismatch error occurs
go to the next step to reset the module to out-of-box condition.