Rockwell Automation Publication 1734-UM013J-EN-P - July 2014
97
Configure the Module in a GuardLogix Controller System
Chapter 5
Follow these steps to configure alarms for each of the safety analog input
channels.
1.
From the Module Properties dialog box, click the Alarm tab.
2.
To configure each channel, click 0, 1, 2, or 3, as appropriate.
3.
To enable the alarm, check the boxes:
•
Enable High High - Low Low Alarms
•
Enable High - Low Alarms
4.
Type the alarm values from -32768…32767 in the appropriate fields,
following these guidelines:
•
The High High alarm value must be greater than or equal to the High
alarm value.
•
The High alarm value must be greater that the Low alarm value.
•
The Low Low alarm value must be less than or equal to the Low alarm
value.
•
These values are based on the Engineering units configured on
.
5.
Configure a deadband value for the High High - Low Low alarms and
High - Low alarms, if desired.
The valid range is 0…32767. The deadband lets the alarm status bit remain
set, despite the alarm condition disappearing, as long as the input data
remains within the deadband of the alarm. These values are based on the
Engineering units configured on
For more information on this feature, see
Summary of Contents for Allen-Bradley 1734-IB8S
Page 1: ...POINT Guard I O Safety Modules Catalog Numbers 1734 IB8S 1734 OB8S 1734 IE4S User Manual ...
Page 4: ...4 Rockwell Automation Publication 1734 UM013J EN P July 2014 Summary of Changes Notes ...
Page 10: ...10 Rockwell Automation Publication 1734 UM013J EN P July 2014 Table of Contents ...
Page 14: ...14 Rockwell Automation Publication 1734 UM013J EN P July 2014 Preface Notes ...
Page 186: ...186 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix D Safety Data Notes ...
Page 211: ......