Chapter 5
Configure the Module in a GuardLogix Controller System
4.
Specify the general properties of the Ethernet adapter.
a. In the Name field of the New Module dialog box, type the name of the
1734 Ethernet adapter.
b. In the Description field, type a description, if desired.
c. In the IP Address field, type the IP address.
5.
Click Change to edit the Ethernet Adapter’s Module Definition.
.
a. In the Revision fields, choose the major and minor revisions.
b. From the Electronic Keying pull-down menu, choose the appropriate
keying method.
IMPORTANT
1734-AENT adapter firmware must be major revision 3 or later to
support POINT Guard I/O modules.
Choose
Description
Exact Match
Module and type series must exactly match or the module will be rejected by the
controller.
Compatible Module
Controller will check module type and revision for compatibility. Compatible
modules that match or are newer will be accepted.
Disable Keying
Controller will check module type, but will accept any version.
Do not choose
Disable Keying.
Summary of Contents for Allen-Bradley 1734-IB8S
Page 1: ...POINT Guard I O Safety Modules Catalog Numbers 1734 IB8S 1734 OB8S 1734 IE4S User Manual ...
Page 4: ...4 Rockwell Automation Publication 1734 UM013J EN P July 2014 Summary of Changes Notes ...
Page 10: ...10 Rockwell Automation Publication 1734 UM013J EN P July 2014 Table of Contents ...
Page 14: ...14 Rockwell Automation Publication 1734 UM013J EN P July 2014 Preface Notes ...
Page 186: ...186 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix D Safety Data Notes ...
Page 211: ......