Rockwell Automation Publication 1734-UM013J-EN-P - July 2014
61
Install the Module
Chapter 4
Emergency stop button
Door monitoring switch
No
Connect the devices between T0 and I0
and I1, noting that T0 is configured for
24V power supply.
3
Connect the devices between 24V DC
and I0 and I1.
Yes
Connect the device between I0 and T0,
and I1 and T1.
4
Light Curtain
Yes
Connect the OSSD1 and OSSD2 to I0 and
I1, respectively. Connect the 24V power
supply commons.
3 or 4 based on
light curtain
being used
Connected Device
Test Pulse from
Test Output
Connection
Schematic Diagram
Safety
Category
I0
I1
T0
T1
I0
I1
T0
T1
24V DC
I0
I1
T0
T1
OSS
D2
OSS
D1
I0
I1
T0
T1
In -
24V
DC
Com
OSSD2
OSSD1