Rockwell Automation Publication 1734-UM013J-EN-P - July 2014
Appendix A
Indicators
Module
Network Status
Configuration Lock
Indicator
Description
Recommended Action
MS
Off
No power is applied to the module.
Apply power to this connector.
Solid green
The module is operating normally.
None.
Solid red
The module detected an unrecoverable fault.
Cycle power to the module. If problem persists, replace the module.
Flashing green
Device is in the Idle or Standby state.
Configure the module and establish connection.
Flashing red
The module has detected a recoverable fault.
Cycle power to the module or reset the module.
User-initiated firmware update is in progress.
Wait for firmware update to complete.
Flashing red and
green
Module is not configured.
Reconfigure the module. For additional information, inspect Network
Status indicator.
The module is performing its power-cycle diagnostic tests.
Wait for the module to complete its power-cycle diagnostics.
Indicator
Description
Recommended Action
NS
Off
The module is not online with the network or there is no power.
Verify your network is working properly.
Flashing green
Module online with no connections in established state.
Verify your network and module configuration.
The module identified the communication rate of the network but no
connections are established.
Solid green
Module online with connections in established state. The module is
operating normally.
None.
Flashing red
One or more I/O connections is in timed-out state.
Verify your network and module configuration.
A user-initiated firmware update is in progress.
Wait for firmware update to complete.
Solid red
Critical link failure. The module detected an error that prevents it
from communicating on the network, such as a duplicate node
address.
Cycle power to the module. Check node addressing.
Indicator
Description
Recommended Action
LK
(1)
Off
No configuration or configured by a GuardLogix originator.
Validate configuration by a network configuration tool, such as
RSNetWorx software.
Invalid configuration data.
Solid yellow
Locked.
None.
Valid configuration, locked by a network configuration tool, such as
RSNetWorx software.
Flashing yellow
Not locked.
None.
Valid configuration by a network configuration tool, such as
RSNetWorx software.
(1) Not applicable when used with GuardLogix controllers.
Summary of Contents for Allen-Bradley 1734-IB8S
Page 1: ...POINT Guard I O Safety Modules Catalog Numbers 1734 IB8S 1734 OB8S 1734 IE4S User Manual ...
Page 4: ...4 Rockwell Automation Publication 1734 UM013J EN P July 2014 Summary of Changes Notes ...
Page 10: ...10 Rockwell Automation Publication 1734 UM013J EN P July 2014 Table of Contents ...
Page 14: ...14 Rockwell Automation Publication 1734 UM013J EN P July 2014 Preface Notes ...
Page 186: ...186 Rockwell Automation Publication 1734 UM013J EN P July 2014 Appendix D Safety Data Notes ...
Page 211: ......