![Riello 20187643 Installer And User Manual Download Page 6](http://html1.mh-extra.com/html/riello/20187643/20187643_installer-and-user-manual_1459307006.webp)
FAMILY
6
Twin pipes with Ø 80 pipework Ø50 - Ø60 - Ø80)
Thanks to the boiler characteristics, a Ø80 flue gas exhaust pipe can be connected to
the Ø50 - Ø60 - Ø80 piping ranges.
b
For the pipe, you are advised to make a project calculation in order to respect the
relevant regulations in force.
The table shows the standard configurations allowed.
Air suction
1 Bend 90° Ø 80
4.5m pipe Ø80
Flue gas discharge
1 Bend 90° Ø 80
4.5m pipe Ø80
Reduction from Ø80 to Ø50 from Ø80 to Ø60
Flue base bend 90°, Ø50 or Ø60 or Ø80
For ducting pipe lengths see table
The boilers are factory set to:
CH rpm
DHW rpm
Max length pipes (m)
Ø50
Ø60
Ø80
25 IS
6.200
7.600
5
18
98
35 IS
7.300
7.800
2
11
57
Should greater lengths be required, compensate the pressure drop with an increase in the
r.p.m.of the fan, as shown in the adjustments table, to provide the rated heat input.
b
The minimum calibration should not be modified.
Table of adjustments INSIDE CHIMNEY PIPES
twin flue pipe
Fan rotations rpm
Pipes Ø50
Pipes Ø60
Pipes Ø80
∆P
at boiler outlet
CH
DHW
Maximum length (m)
Pa
25 IS
6.200
7.600
5
18
98
174
6.300
7.700
7*
23*
125*
213
6.400
7.800
9*
28*
153*
253
6.500
7.900
11*
33*
181*
292
6.600
8.000
13*
38*
208*
332
6.700
8.100
15*
43*
236*
371
6.800
8.200
17*
48*
263*
410
6.900
8.300
19*
53*
291*
450
7.000
8.400
22*
58*
319*
489
7.100
8.500
24*
63*
346*
528
35 IS
7.300
7.800
2
11
57
190
7.400
7.900
3*
15*
75*
229
7.500
8.000
4*
19*
93*
269
7.600
8.100
6*
22*
112*
308
7.700
8.200
7*
26*
130*
348
7.800
8.300
9*
30*
148*
387
7.900
8.400
10*
33*
166*
426
8.000
8.500
12*
37*
184*
466
8.100
8.600
13*
40*
202*
505
8.200
8.700
15*
44*
220*
544
(*) Maximum length that can be installed ONLY with class H1 discharge pipes.
The Ø50 or Ø60 or Ø80 configurations contain Lab test data. In the event of installations that
differ from the indications in the “standard configurations” and “adjustments” tables, refer to
the equivalent linear lengths below.
b
In any case, the maximum lengths declared in the booklet are guaranteed, and it is
essential not to exceed them.
Linear equivalent in metres Ø80 (m)
COMPONENT
Ø 50
Ø 60
Bend 45°
12.3
5
Bend 90°
19.6
8
Extension 0.5m
6.1
2.5
Extension 1.0m
13.5
5.5
Extension 2.0m
29.5
12
chimney for ducting
Ø 50 mm or Ø 60 mm
or Ø 80 mm
length
90° bends
Ø 80 mm
Ø 80 mm
4,5 m Ø 80 mm
Ø 80-60 mm
or Ø 80-50 mm
reduction
90° bend
Ø 50 mm
Ø 60 mm
or Ø 80 mm
2.8
Installation on collective flues in positive pressure
The collective flue is a flue gas exhaust system suitable for collecting and expelling the
combustion products of several appliances installed on several floors of a building.
The positive pressure collective flues can only be used for type C condensing appliances.
Therefore the B53P/B23P configuration is forbidden. The installation of boilers under
collective pressure flues is allowed exclusively in G20. The boiler is sized to operate
correctly up to a maximum internal pressure of the flue no higher than the value of 25 Pa.
Check that the fan speed corresponds to what is shown in the “technical data” table.
Make sure that the air intake and exhaust pipes of the combustion products are watertight.
WARNINGS:
b
The appliances connected to a collective pipe must all be of the same type and have
equivalent combustion characteristics.
b
The number of devices connected to a positive pressure collective pipe is defined
by the flue designer
.
The boiler is designed to be connected to a collective flue sized to operate in conditions
where the static pressure of the collective flue pipe can exceed the static pressure of the
collective air duct of 25 Pa in the condition in which n-1 boilers work at maximum rated heat
input and 1 boiler at the minimum rated heat input allowed by the controls.
b
The minimum permissible pressure difference between the flue gas outlet and the
combustion air inlet is -200 Pa (including - 100 Pa of wind pressure).
For both types of exhaust, further accessories are available (curves, extensions, terminals,
etc.) which make possible the flue gas exhaust configurations foreseen in the boiler booklet.
b
The pipes must be installed in such a way as to avoid condensation sticking which
would prevent the correct evacuation of the combustion products.
b
A data plate must be present at the connection point with the collective flue pipe.
The plate must include at least the following information:
-
the collective flue is sized for boilers C(10) type
-
the maximum permissible mass flow of the combustion products in kg/h
-
the dimensions of the connection to the common pipes
-
a warning concerning the openings for the air outlet and the entry of the combu-
stion products of the collective pressure pipe; these openings must be closed and
their tightness must be checked when the boiler is disconnected
-
the name of the manufacturer of the collective smoke pipe or its identification
symbol.
b
See applicable legislation for the discharge of the combustion products as well as
local regulations.
b
The flue gas pipe must be suitably selected based on the parameters shown below
.
maximum length
minimum length
UM
ø 60-100
4,5
0,5
m
ø 80
4,5
0,5
m
ø 80/125
4,5
0,5
m
b
The terminal of the collective pipe must generate an upward air current.
b
Before attempting any operation, disconnect the appliance from the electrical supply.
b
Before assembling, lubricate the gaskets with a non-corrosive glide lubricant.
b
The flue gases discharge pipe should be inclined, if the pipe is horizontal, by 3°
towards the boiler.
b
The number and characteristics of the exhaust ventilation devices which are the real
characteristics of the flue itself.
Summary of Contents for 20187643
Page 116: ...Cod 20187602 06 22 Ed 6...