4.15 INFO
The
INFO
function can be used to display a series of data regarding the system. The passage
from one parameter to the next takes place by pressing the
“+”
and
“-”
keys.
b
Depending on the system configuration some of the info might not be available.
SCREED HEATER OPERATING HOURS
DELIVERY PROBE
RETURN PROBE
DOMESTIC HOT WATER PROBE
HIGH STORAGE TANK PROBE
LOW STORAGE TANK PROBE
SOLAR COLLECTOR
FLUE GAS PROBE
OUTDOOR TEMPERATURE SENSOR
EXT T FOR THERMOREG
FLOW METER / DHW SETPOINT OT+
FAN
DELIVERY ZONE 1
DELIVERY ZONE 2
FLUE GAS PROBE OPERATING HOURS
MAIN ZONE SET-POINT
ZONE 1 SET-POINT
ZONE 2 SET-POINT
SYSTEM PRESSURE
CURVE (combustion)
HEAT PUMP DELIVERY
HEAT PUMP RETURN
HEAT PUMP EXT. TEMP.
TREFR LOW PRESSURE PIPE
TREFR HIGH PRESSURE PIPE
TREFR CONDENSER
TREFR HEAT EXCHANGER
HEAT PUMP OPERATING MODE
HEAT PUMP FREQUENCY
HEAT PUMP COMPRESSOR TIME
HEAT PUMP CIRCULATOR TIME
HEAT PUMP FLOW SWITCH
HEAT PUMP OUTPUT
HEAT PUMP SET-POINT
NEXT ANTI-LEGIONELLA
4.16 Combustion info
T
INFO
function can be used to display a series of data regarding the system.
-
Select TECHNICAL
COMBUSTION MONITORING
INFO.
The passage from one parameter to the next takes place by pressing the
“+”
and
“-”
keys.
INFO page 1
1
Number of calibrations at minimum power
(correct combustion test identified with code 18)
2
Number of calibrations at the speed of 3500 RPM
(correct combustion test identified with code 18)
3
Number of calibrations at default power RANGE RATED
(correct combustion test identified with code 18)
4
Number of calibrations at maximum boiler output
(correct combustion test identified with code 18)
5
Last calibration [1] PowMin - [2] 3500rpm - [4] Range Rated - [8] PowMax
6
Peak Iono of the last calibration
7
Reference value of PWM effort fan control
8
PWM fan control
9
Number of DataFlash AB writes
10
Number of DataFlash CD writes
INFO page 2.A
11.A
Iono curve correction at minimum power
(defined with correct combustion test 18)
12.A
Iono curve correction at the speed of 3500 RPM
(defined with correct combustion test 18)
13.A
Iono curve correction at default power RANGE RATED
(defined with correct combustion test 18)
14.A
Iono curve correction at maximum boiler output
(defined with correct combustion test 18)
15.A
Calibration test check performed [1] PowMin - [2] 3500rpm - [4] Range Rated - [8]
PowMax
16.A
Time counter [min] from last calibration to minimum power
17.A
Time counter [min] from last speed calibration of 3500 RPM
18.A
Time counter [min] from last calibration to default power RANGE RATED
19.A
Time counter [min] from last calibration to boiler maximum
20.A
Time counter [min] restart timing of calibration (maximum timeout to make the 4
calibrations)
INFO page 2.B (
Identified with the value 12345 on line 11 - It changes status automatically
every 10 seconds)
11.B
12345
12.B
Iono Curve Auto-Correction Number at minimum power
(auto correction for alarm)
13.B
Iono Curve Auto-Correction Number at the speed of 3500 RPM
(auto correction for alarm)
14.B
Iono Curve Auto-Correction Number at default power RANGE RATED
(auto correction for alarm)
15.B
Iono Curve Auto-Correction Number at maximum output
(auto correction for alarm)
16.B
Maximum power calibration coefficient
17.B
Range Rated power calibration coefficient
18.B
Minimum power calibration coefficient
19.B
FIX CO2 ALL PLUS value
20.B
DEC CO2 ALL PLUS value
INFO page 3 (Chronological order of the last 5 alarms/tests and related FAN speeds)
21
Identification code (17-18) of a test performed to verify correct combustion # 1
22
RPM/100 where alarm and/or test # 1 occurred
23
Alarm code and/or identification code (17-18) of a test performed to verify correct
combustion # 2
24
RPM/100 where alarm and/or test # 2 occurred
25
Alarm code and/or identification code (17-18) of a test performed to verify correct
combustion # 3
26
RPM/100 where alarm and/or test # 3 occurred
27
Alarm code and/or identification code (17-18) of a test performed to verify correct
combustion # 4
28
RPM/100 where alarm and/or test # 4 occurred
29
Alarm code and/or identification code (17-18) of a test performed to verify correct
combustion # 5
30
RPM/100 where alarm and/or test # 5 occurred
4.17 Error history
The ERROR HISTORY function is automatically enabled only after the machine has been
powered up for at least 2 consecutive hours, during this period of time any alarms that arise
would not be saved in the “error history”. The alarms can be displayed in chronological
order, from the most recent to the oldest, up to a maximum of 50 alarms; to display the
error history:
-
select TECHNICAL
ERROR HISTORY
EXHAUST PROBE RESET
COMBUSTION ANALYSIS
CALIBRATION
RANGE RATED
ERROR HISTORY
INSTALLER
TECHNICAL
-
for each alarms a sequential number is displayed, an error code and the date and time
the alarm occurred.
FAN ERROR
1 - 10:30 18/11/2020
E030
USE ARROW KEYS TO SEE OTHER ANOMALIES
Note
: Once enabled, the ERROR HISTORY function can no longer be disabled; there is no
procedure for resetting the error history.
If an alarm repeats consecutively, it is saved only once.
4.18
Water tank configuration
b
The boiler leaves the factory pre-configured for managing a water tank with a
thermostat (tank type parameter = 0
).
To modify the configuration of the water tank:
-
select TECHNICAL
WATER TANK
CALIBRATION
TECHNICAL
INSTALLER
COMBUSTION ANALYSIS
EXHAUST PROBE RESET
WATER TANK
-
choose from the following options:
WATER TANK
INSTALLER
REMOVE WATER TANK
TANK TYPE
TANK FLOW TEMP
TANK TYPE:
this parameter allows you to set the type of the water tank. Set the value to 1
to select a water tank with probe, set the value to 0 to select a water tank with thermostat
(factory setting).
REMOVE WATER TANK:
this function is used to disable the operation of the water tank;
water tank disabled, the relative configuration menu is no longer accessible. If you wish to
add a storage cylinder again, after a previous removal, follow the instructions in paragraph
TANK FLOW TEMP:
the parameter allows you to set the delivery temperature of the boiler
to the water tank when the SLIDING OUTLET function is not active. The factory setting is
80°C.