4.19 Temporary switch-off
-
Set the boiler to OFF .
While the electrical supply and the fuel supply remain active, the boiler is protected by the
systems:
-
heating anti-freeze
: this function is activated if the temperature measured by the flow sensor
drops below 5°C. A heat request is generated in this phase with the ignition of the burner at
minimum output, which is maintained until the outlet water temperature reaches 35° C;
-
domestic hot water anti-freeze (only if water tank connected)
: this function is
activated if the temperature measured by the water tank probe drops below 5°C. A heat
request is generated in this phase with the ignition of the burner at minimum output,
which is maintained until the outlet water temperature reaches 55° C.
b
The activation of the ANTI-FREEZE function is indicated by a scrolling message on
the foot of the REC10CH display.
-
circulator anti-locking
: the circulator activates every 24 hours of stoppage for 30
seconds.
4.20 Switching off for lengthy periods
The long term non use of the
FAMILY
boiler causes the following operations to be carried
out:
-
set the boiler to OFF
-
set the system’s main switch to “off”
-
close the fuel and water taps of the heating and domestic hot water system.
In this case, the anti-freeze and anti-blocking systems are deactivated. Drain the heating
and domestic water system if there is any risk of freezing.
4.21 System reset
b
This operation must be carried out only by professionally qualified personnel.
Whenever necessary, it is possible to restore the factory settings by carrying out a SYSTEM
RESET:
-
access to menu TECHNICAL
INSTALLATION
SYSTEM RESET
CONFIRM or CANCEL
CANCEL
CONFIRM
ZONES MANAGER
SENSOR CALIBRATION
SYSTEM RESET
INSTALLER
INSTALLATION
RANGE RATED
WEATHER COMPENSATION
PARAMETERS
CALIBRATION
INSTALLATION
INSTALLER
TECHNICAL
Note:
After a reset it is necessary to carry out a new configuration of the system; for details
about this procedure, see the following section.
4.22
System configuration
b
This operation must be carried out only by professionally qualified personnel.
When restarting after a replacement of the REC10CH rather than after a “SYSTEM
RESET”, the remote control an initial screen with the firmware revision. Pressing “
ENTER
”
starts a guided procedure for configuring the system:
PRESS ANY KEY TO CONTINUE
Rxx.xx
REC10REXPH-N
-
select LANGUAGE: ENGLISH
-
setting TIME and DATE
ENTER TIME AND DATE
12
17
09/04/2021
:
TIME & DATE
-
setting the operating mode of the REC10CH:
MASTER
: select this option when the REC10CH is also a MACHINE INTERFACE.
-
configuration selection:
MAIN PCB
: to reset the current boiler configuration on REC10CH MASTER and finish
the operation
NEW
: to set a new system configuration restoring the factory setting of the parameters
NEW
MAIN PCB
SELECT THE TYPE OF
CONFIGURATION
Whenever a “NEW” configuration is selected, proceed as follows:
-
select:
ON BOARD
: if the REC10CH is used only as a system interface and not as an ambient
regulator
AMBIENT
: if the REC10CH is used as a system interface and also as an ambient
regulator of the zone where it is installed
ON BOARD
WHERE IS THE MULTI ZONE INSTALLED?
AMBIENT
BOILER
-
select the type of boiler on:
-
CH ONLY: if the boiler does not manage the domestic hot water (case A)
-
HW TANK: if the boiler manages a domestic hot water tank. Note: in this case the
specific type of domestic hot water request will be requested THERMOSTAT (case B) or
TEMPERATURE PROBE (case C)
-
if the water tank with probe is selected you are also asked whether to manage also the
solar heating system: answer No to this question.
INSTANTANEOUS
HW TANK
CH ONLY
SELECT THE PLANT CONFIGURATION
PLANT
Once the guided procedure has finished, the REC10CH will go to the initial screen.
Then proceed with the reprogramming of the boiler, carrying out the operations described
in the section “4.2 Programming the boiler”.
4.23
Boiler configuration
The BOILER menu allows you to change the hydraulic configuration without necessarily
having to go through a SYSTEM RESET operation.The HYDRAULIC CONF parameter can
assume values between 0 and 4 with the following meaning:
0 = only heating boiler
1 = instantaneous boiler with flowswitch
2 = instantaneous boiler with flowmeter
3 = only heating boiler with water tank with probe
4 = only heating boiler with water tank with thermostat
4.24 Replacing the REC10CH Master
b
The system configuration operations need to be carried out by professionally
qualified personnel of the Technical Assistance Centre.
When replacing the REC10CH MASTER, at the subsequent restart it displays an initial
screen with the firmware revision. Pressing “
ENTER
” starts a guided procedure for
configuring the system, see the section “Configuring the system”.
Follow the procedure and carry out the MAIN PCB type of configuration
.
PRESS ANY KEY TO CONTINUE
Rxx.xx
REC10REXPH-N
NEW
MAIN PCB
SELECT THE TYPE OF
CONFIGURATION
4.25 Replacing the MAIN PCB board
The system configuration operations need to be carried out by professionally qualified
personnel of the Technical Assistance Centre. The systems continually carries out a
consistency control between the configuration data saved on the MAIN PCB electronic board
and that saved in the REC; therefore, when replacing the MAIN PCB electronic board, it might
happen that the system detects an inconsistency between the data saved on the MAIN PCB
and that in the REC. In this case, the latter will ask the user which of the two configurations is to
be considered valid; selecting to recuperate the configuration from the REC itself it is possible
to avoid reconfiguring the machine:
-
select REC10CH.
MAIN PCB
REC10
SELECT THE TYPE OF
CONFIGURATION
4.26 Combustion Control Parameters
Even if the parameters regarding the new ACC combustion control system (active
combustion control) are preset in the factory, it might be necessary to programme them, this
is in the case where both electronic boards (MAIN PCB and REC10CH MASTER) need to
be replaced at the same time.
-
set SERVICE password
-
select TECHNICAL
COMBUSTION MONITORING