81
installation-power vent
920-210b
09.22.20
10
CV72EPV/CB72EPV/CB40EPV/CC40EPV/CV40EPV/CV60EPV
Inline Power Vent Vertical or Hortizontal Installation Instructions
Confined spaces (chase, closet, attic, behind a wall):
• 3” (76 mm) clearance is required on top of the power vent in a horizontal configuration (Diagram 2).
• 2” (51 mm) clearance is required on the sides and bottom in a horizontal configuration (Diagram 2).
• 1’ (305 mm) clearance is required from the ends of the power vent in a horizontal configuration (Diagram 1).
• 2” (51 mm) clearance is required on sides in a vertical configuration (Diagram 2).
• 1’ clearance is required on ends in a vertical configuration (Diagram 1).
• A framed access hole with dimensions of 12” x 16” (305 mm x 406 mm) is required to access the access panel if the inline power vent is
placed behind a wall (Diagram 3).
• The access hole can be covered with an open-air louver cover which allows 50% open air.
• The power vent must be installed where it can be easily accessed for servicing. An access hole as noted below, or an attic space, would be
suitable.
Diagram 1
Diagram 2
Diagram 3
Diagram 4
Gas Power Vent Installation Clearance Requirements
Inline Power Vent Terminations
12 in
(305 mm)
12 in
(305 mm)
12 in
(305 mm)
16 in
(406 mm)
2 in
(51 mm)
2 in
(51 mm)
3 in
(76 mm)
Gas Power Vent Installation Clearance Requirements - Inline Power Vent Terminations
920-210b
09.22.20
10
CV72EPV/CB72EPV/CB40EPV/CC40EPV/CV40EPV/CV60EPV
Inline Power Vent Vertical or Hortizontal Installation Instructions
Confined spaces (chase, closet, attic, behind a wall):
• 3” (76 mm) clearance is required on top of the power vent in a horizontal configuration (Diagram 2).
• 2” (51 mm) clearance is required on the sides and bottom in a horizontal configuration (Diagram 2).
• 1’ (305 mm) clearance is required from the ends of the power vent in a horizontal configuration (Diagram 1).
• 2” (51 mm) clearance is required on sides in a vertical configuration (Diagram 2).
• 1’ clearance is required on ends in a vertical configuration (Diagram 1).
• A framed access hole with dimensions of 12” x 16” (305 mm x 406 mm) is required to access the access panel if the inline power vent is
placed behind a wall (Diagram 3).
• The access hole can be covered with an open-air louver cover which allows 50% open air.
• The power vent must be installed where it can be easily accessed for servicing. An access hole as noted below, or an attic space, would be
suitable.
Diagram 1
Diagram 2
Diagram 3
Diagram 4
Gas Power Vent Installation Clearance Requirements
Inline Power Vent Terminations
12 in
(305 mm)
12 in
(305 mm)
12 in
(305 mm)
16 in
(406 mm)
2 in
(51 mm)
2 in
(51 mm)
3 in
(76 mm)
A
B
A
12" (305 mm)
B
2" (51 mm)
C
3" (78 mm)
D
16" (406 mm)
A
B
A
C
D