installation - general
Clearances - Bench Installation
Flue Clearances to Combustibles
Horizontal - Top
3" (76 mm)
Horizontal - Side
2" (51 mm)
Horizontal - Bottom
2" (51 mm)
Vertical
2" (51 mm)
Passing through wall/
floor/ceiling - when
firestop is used.
1-1/2" (38 mm)
Clearance
Dimension
Measured From:
A: Mantel height (min.)
**
Top of fireplace opening
B: Sidewall (on one side) min.
8" (203 mm)
Side of fireplace opening
C: Enclosure inside cavity width (min.)
71-3/4" (1822 mm)
Side wall
D: Mantel depth (max.)
**
E: Convection air outlet (min.)
180 sq. in.
Top, front of enclosure
F: Framing depth (min.)
22-1/4" (565 mm)
From back wall to chase front
G: Opening height
18" (457 mm)
Bottom/top of fireplace opening
H: Chase enclosure (min.)
52" (1321 mm) to 81-1/4"
(2064 mm) max.
From base of unit/floor to underside
of enclosure top
I: Ceiling height (min.)
81-1/4" (2064 mm)
Measured from base of appliance
J: Convection air outlet opening offset (max.)
2" (51 mm)
Max offset from top of chase
enclosure
K: Convection air outlet opening width (min.)
10" (254 mm)
L : Convection air outlet opening height (min.)
1-1/2" (38 mm)
M: Ceiling clearance (min.)
3" (76 mm)
Top convection air outlet only
N: Clearance to sprinkler head
36" (914 mm)
Perpendicular from chase grill
Hearth
0"
No hearth required
** See mantel clearances chart in the manual.
* For clearances greater than 81 1/4" (2064 mm), see flush installation clearances in this manual. The size of the
ventilation opening is reduced from 180 sq. in. to 120 sq. in.
The clearances listed below are minimum requirements for either side of this see-through fireplace, unless otherwise noted.
A major cause of chimney-related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this
fireplace and vent system are installed in accordance with the instructions in this manual.
NO
TES
• This appliance uses 5" x 8" (127 mm
x 203 mm) venting for non power vent
applications. For power vent applications,
vent pipe must be reduced to 4" x 6 5/8"
4" x 6 5/8"
(102 mm x 168 mm).
(102 mm x 168 mm).
•
• HeatWave not
HeatWave not permitted in bench
permitted in bench
applications.
applications.
CA
UTION
• EXTREME RISK OF FIRE if these clearances (air space) to
combustible materials are not adhered to. It is of greatest
importance that this fireplace and vent system are installed in
accordance with the instructions in this manual.
• The top, back, and sides of the fireplace are defined by standoffs. The metal
ends of the standoff may NOT be recessed into combustible construction.
NO
TE
• Bench installation is when the chase enclosure height is at a minimum of 52" (1321 mm) to a maximum of 81-1/4" (2064 mm). If the bench installation
is completed at the minimum height, a shelf, counter top, or other finsh can be installed.
B
C
D
F
G
H
I
M
J
E
L
K
A
Ceiling
M
Chase grill
Sprinkler
Side view
N
*A minimum of 120 square inches of open area, not lower than 0-2" (51 mm) from top of enclosure, is
required for all installations.