SECTION 15: DUCT CONSIDERATIONS
The air handler has been designed to operate at the
specific air
v
ol
u
me and external static press
u
re that
w
as ordered (air handlers set-
u
p to accept an
external static press
u
re (ESP) of 1 in
w
c (2.5 mbar).
This static press
u
re is generated by any additional
components that are added to the heater (i.e. inlet
hood, filter section, dampers, d
u
ct
w
ork, discharge
heads, etc). Additional static press
u
re beyond that
ordered
w
ill affect the performance of the air handler
and lessen the air
v
ol
u
me that can be deli
v
ered.
Proper engineering methods need to be employed
w
hen calc
u
lating d
u
ct and component static press
u
re
(i.e. 2009 ASHRAE Handbook - F
u
ndamentals,
Chapter 21). Accessory press
u
re drops are a
v
ailable
on
.
The system d
u
ct
w
ork m
u
st comply
w
ith Sheet Metal
and Air Conditioning Contractors Nationals
Association (SMACNA) or any other recognized
standards.
As a general r
u
le, all discharge d
u
cts sho
u
ld ha
v
e a
straight r
u
n of at least 3 hydra
u
lic d
u
ct diameters
after the air handler before adding any fittings,
elbo
w
s, restrictions, etc. Ret
u
rn d
u
cts sho
u
ld ha
v
e
the same straight r
u
n before attaching to the
u
nit.
Hydra
u
lic d
u
ct diameter for ro
u
nd d
u
cts in inches:
Dh = d
Dh: hydra
u
lic diameter
d: ro
u
nd d
u
ct inside diameter
Hydra
u
lic d
u
ct diameter for rectang
u
lar d
u
cts (in
inches):
Dh = (2*H*W)/(H+W)
Dh: hydra
u
lic diameter
H: rectang
u
lar d
u
ct inside height
W: rectang
u
lar d
u
ct inside
w
idth
The air handler is not designed to s
u
pport the
w
eight
of d
u
ct
w
ork. D
u
ct
w
ork m
u
st be constr
u
cted in a
fashion that is self-s
u
pporting. D
u
ct
w
ork sho
u
ld be
straight, elbo
w
s sho
u
ld be minimal and any
transitions sho
u
ld be smooth.
Depending on the options ordered
w
ith the air
handler, flanges (either external or internal) may be
pro
v
ided to facilitate connection of d
u
ct
w
ork. In
cases
w
here flanges are not pro
v
ided, flat s
u
rfaces
on the exterior skin of the air handler are pro
v
ided to
facilitate connection of d
u
ct
w
ork.
15.1 Inlet Duct Work
Inlet d
u
ct
w
ork height and
w
idth m
u
st be no smaller
than the air handler inlet height and
w
idth and s
u
pply
only fresh air to the air handler. (
for inlet dimensions).
15.2 Return Duct Work
Inlet d
u
ct
w
ork height and
w
idth m
u
st be no smaller
than the air handler inlet height and
w
idth and s
u
pply
only fresh air to the air handler. (
for inlet dimensions).
15.3 Dischar
g
e Duct Work
for minim
u
m discharge
d
u
ct sizes by model. Refer to
for
discharge d
u
ct size req
u
ired for connecting to heater
(BD or RD), these dimensions pro
v
ide clearance for
d
u
ct flange to blo
w
er mo
u
nting bolts.
Cut/Pinch Hazard
Wear protective gear
during installation,
operation and
service.
Edges are sharp.
Falling Hazard
Use proper safety
equipment and prac-
tices to avoid falling.
WARNING
Failure to follow these instructions can result
in death, injury or property damage.
Summary of Contents for 2005
Page 2: ......
Page 4: ......
Page 8: ......
Page 10: ......
Page 31: ...SECTION 7 ROOF CURB 21 of 147 FIGURE 12 Curb Mounting Air Handler Roof Curb Fastening Detail...
Page 154: ...B SERIES INSTALLATION OPERATION AND SERVICE MANUAL 144 of 147...
Page 158: ......
Page 160: ......
Page 161: ......
Page 162: ......