B-S
ERIES
I
NSTALLATION
, O
PERATION
AND
S
ERVICE
M
ANUAL
142 of 147
22.6A44 Amplifier - Field Service Checklist
SYMPTOM
POSSIBLE CAUSE
A.
No gas fl ow.
1. Valve improperly installed.
B.
Continuous low fi re (electronics ok).
2. Open circuit in modulator coil.
3. Plunger missing, jammed or improperly installed.
4. Ruptured main or balancing diaphragm.
C.
Continuous Low Fire (electronics problem)
5. No voltage to the amplifi er.
6. Short in modulator coil circuit.
7. Short in TS144 circuit.
8. Faulty amplifi er.
D.
Incorrect Low Fire
9. Incorrect by-pass metering valve adjustment.
10. Excessive negative burner pressure.
E.
Continuous Minimum Discharge Air Temperature
11. Faulty amplifi er.
12. Short in T244 or TS244/TD244 circuit
13. Incorrect space temperature calibration.
F.
Incorrect Max. or Min. Discharge Air Temperature.
14. Improper TS144 location.
15. Incorrect discharge air temperature calibrations
G.
Continuous High Fire (electronics ok)
16. Foreign material holding valve open.
17. Plunger jammed.
H.
Continuous High Fire. (electronics problem)
18. Open circuit in TS144
I.
Incorrect High Fire
19. Inlet pressure too low.
20. Incorrect outlet pressure adjustment.
J.
Continuous Maximum Discharge Air Temperature
21. Faulty amplifi er.
22. Open circuit in T244 to TS244/TD244
23. Incorrect space temperature calibration.
K.
Burned out Transformer. No Voltage to Amplifi er
24. Short in modulator coil circuit.
L.
Incorrect Space Temperature.
25. Incorrect maximum discharge air temperature
setting (A1044).
26. Incorrect minimum discharge air temperature
setting (A1044).
27. Insufficient burner capacity.
28. Incorrect space temperature calibration.
*Control circuits external to the Series 44 can cause burner malfunction. Always check manual valve to be certain gas is on, and check limit controls
for normal operation.
Summary of Contents for 2005
Page 2: ......
Page 4: ......
Page 8: ......
Page 10: ......
Page 31: ...SECTION 7 ROOF CURB 21 of 147 FIGURE 12 Curb Mounting Air Handler Roof Curb Fastening Detail...
Page 154: ...B SERIES INSTALLATION OPERATION AND SERVICE MANUAL 144 of 147...
Page 158: ......
Page 160: ......
Page 161: ......
Page 162: ......