SECTION 1
8
: S
EQUENCE
OF
O
PERATION
109 of 147
Table 17: Confi
g
uration Chart
FIGURE 71: Air Handler Styles
Air Handler
Confi
g
uration
Air Flow
Air Volume
Control
Make Up Air (MUA)
100% O
u
tside Air
Constant
-
Fixed Recirc
u
lation (FR)
Non-adj
u
stable ratio of
20% o
u
tside air and
80% ret
u
rn air
Constant
-
Air Management (AM)
Adj
u
stable ratio of 20%
o
u
tside air and 80%
ret
u
rn air to 100% o
u
t-
side air and 0% ret
u
rn
air
Constant
B
u
ilding Press
u
re
Controls O
u
tside/
Ret
u
rn Air Ratio
Variable Air Vol
u
me (VAV)
100% O
u
tside Air
Variable
50% -
100%
B
u
ilding Press
u
re
Controls Air
Vol
u
me
Req
u
irement
DAMPER
FLOATING
DAMPER
FLOATING
MUA - MAKE UP AIR (All Models)
FR - FIXED RETURN (All Models)
VAV - VARIABLE AIR VOLUME (2010 and 2010B)
AM - AIR MANAGEMENT (2010 and 2010B)
VAV - VARIABLE AIR VOLUME (2020 and 2030)
AM - AIR MANAGEMENT (2020 and 2030)
Floating Damper