17.7 Carbon Dioxide Interlocks
All air handlers that recirc
u
late air from the heated
space req
u
ire either a control to limit the temperat
u
re
rise in proportion to the amo
u
nt of o
u
tdoor air or the
u
se of a room carbon dioxide sensor. The carbon
dioxide sensor is field pro
v
ided and set to maintain a
CO2 concentration belo
w
5,000 ppm. For the
additional
w
iring to accommodate this req
u
irement
for the FR and MUA style air handler,
. For the additional
w
iring to accommodate
this req
u
irement for the AM and VAV style air
handlers
for 2010 and 2010B.
See
for models 2020 and 2030.
FIGURE 56: CO2 Sensor Interlock for FR and
MUA Style
FIGURE 57: CO2 Sensor Interlock for AM and VAV
Style (2010 and 2010B)
FIGURE 5
8
: CO2 Sensor Interlock for AM and VAV
Style (2020 and 2030)
17.
8
Control Options
17.
8
.1 Mild Weather Outside Air Stat
This option is designed to t
u
rn the b
u
rner off
w
hen
the incoming o
u
tside air is at or abo
v
e the
temperat
u
re setpoint. The blo
w
er is allo
w
ed to r
u
n for
contin
u
ed
v
entilation. The mild
w
eather o
u
tside air
stat is located in the control enclos
u
re. It has an
adj
u
stable setting bet
w
een -20° F (-29° C) and
100° F (38° C).
49
48
CO2 Sensor
49A
NC
C
Located On The Main Diagram
CO2 Sensor Wiring By Others
Modulating
Regulating
Valve
This Replaces The MRV Wiring
Part Number
Description
Models
13205105
CO2 Sensor Interlock
FR and MUA
CO2 Sensor Wiring By Others
2
CO2 Sensor
Pressure
Building
W
B
Modulating
Damper Motor
Switch or
Photohelic
CR7
CR7
CR7
63
Operation:
Damper Is Forced Into 100% Outside Air Until
CR7 Is Energized By The CO2 Sensor
Allowing The Damper To Modulate
When The CO2 Sensor Reaches The Set Point
The Sensor Contacts Will Open Deenergizing CR7
1
Relay CR7 Connections Are Located Between The
Damper Motor And The Building Pressure Switch or Photohelic
L
H
61
60
62
R
Part Number
Description
Models
13205106
CO2 Sensor Interlock
2010 and 2010B
CO2 Sensor Wiring By Others
2
CO
2
Sensor
Pressure
Building
L3
L2
Modulating
Damper Motor
Switch or
Photohelic
CR7
CR7
CR7
63
Operation:
Damper Is Forced Into 100% Outside Air Until
CR7 Is Energized By The CO2 Sensor
Allowing The Damper To Modulate
When The CO2 Sensor Reaches The Set Point
The Sensor Contacts Will Open Deenergizing CR7
1
Relay CR7 Connections Are Located Between The
Damper Motor And The Building Pressure Switch or Photohelic
L
H
1
60
62
60A
62A
Part Number
Description
Models
13205106
CO2 Sensor Interlock
2020 and 2030
OA STAT
9
9A
RED
BLUE
SET AT 85° F (29° C)
MOUNTED AT PROFILE PLATE
TO TEST: SET DIAL TO MAX TEMP
UNIT OPERATES
SET DIAL TO MIN TEMP
UNIT SHUTS DOWN
Part Number
Description
Models
80930
Mild Weather
O
u
tside Air Stat
All Models
Summary of Contents for 2005
Page 2: ......
Page 4: ......
Page 8: ......
Page 10: ......
Page 31: ...SECTION 7 ROOF CURB 21 of 147 FIGURE 12 Curb Mounting Air Handler Roof Curb Fastening Detail...
Page 154: ...B SERIES INSTALLATION OPERATION AND SERVICE MANUAL 144 of 147...
Page 158: ......
Page 160: ......
Page 161: ......
Page 162: ......