Transport, Set-up and Connection
4 — 18
04_0124_0708GB
Please also refer to the ”General Technical Description” or the electri-
cal circuit diagram for the electrical connection values.
Refer also to chapter: ”General Technical Description” -- section:
”Technical data” and “rating plate” for more details.
Heavy current
Work on the electrical system and equipment of the machine must
be carried out by a qualified electrician or by instructed persons un-
der the supervision and guidance of a qualified electrician and in
accordance with electrical engineering rules and regulations.
The electrical connection must be made on the basis of the electrical
circuit diagram supplied.
The electrical circuit diagram can be found in the machine spare
parts list.
Caution
Do not turn the main switch on at this stage.
The main switch must remain locked until the entire system has been
completely assembled.
Electrical installation prerequisites should be checked by a qualified
electrician before connection work begins.
-- The connected load of the existing electrical installation must be
sufficient for the machine.
-- Please refer to the technical data for the maximum back-up fuse
values.
-- The installation should always be connected to a special feed
point.
-- All 3 phases and the PE (Potential Earth) protective conductor
must be present.
Continuation next side
4.11 Electrical connection
Prerequisites