MVI56-PDPMV1 ♦ ControlLogix Platform
Start Here
PROFIBUS DPV1 Master
User Manual
Page 57 of 251
ProSoft Technology, Inc.
3
Fill the module properties as required:
Parameter
Value
Name
Enter a module identification string. Example: MVI56PDPMV1_2
Description
Enter a description for the module. Example: ProSoft communication
module for PROFIBUS communication.
Comm Format
Select
DATA-INT
Slot
Enter the slot number in the rack where the MVI56-PDPMV1 module is
located.
Input Assembly
Instance
1
Input Size
Enter the number of words per backplane input block to copy from the
module to the processor. The allowable range is from
12
TO
250
words.
Each input block will reserve 8 words for general purposes (CRC, block/CIP
handshaking). The remainder is reserved for PROFIBUS input data.
Output Assembly
Instance
2
Output Size
Enter the number of words per backplane output block to copy from the
module to the processor. The allowable range is from
5
TO
248
words. Each
output block will reserve 5 words for general purposes (CRC and block
handshaking). The remainder is reserved for PROFIBUS output data.
Configuration
Assembly Instance
4
Configuration Size
0
4
Click
OK
to confirm. The new module is now visible:
5
Expand the
Tasks
folder, and then expand the
MainTask
folder.
6
On the
MainProgram
folder, click the right mouse button to open a shortcut
menu. On the shortcut menu, choose
N
EW
R
OUTINE
.
7
In the
New Routine
dialog box, enter the name and description of your
routine, and then click
OK
.