Fill the module properties as follows:
Parameter
Value
Name
Enter a module identification string. Example: MVI56PDPMV1
Description
Enter a description for the module. Example: ProSoft
communication module for PROFIBUS communication.
Comm Format
Select
DATA-INT
Slot
Enter the slot number in the rack where the MVI56-PDPMV1
module is located.
Input Assembly Instance
1
Input Size
Enter the number of words per backplane input block to copy from
the module to the processor. The allowable range is from 12 to
250 words. Each input block will reserve 8 words for general
purposes (CRC, block/CIP handshaking). The remainder is
reserved for PROFIBUS input data.
Output Assembly Instance
2
Output Size
Enter the number of words per backplane output block to copy
from the module to the processor. The allowable range is from 5
to 248 words. Each output block will reserve 5 words for general
purposes (CRC and block handshaking). The remainder is
reserved for PROFIBUS output data.
Configuration Assembly
Instance
4
Configuration Size
0
4
The following illustration shows an example for a local rack application where
the module was set with the maximum backplane I/O sizes (250/248 words).