MVI56-PDPMV1 ♦ ControlLogix Platform
Diagnostics and Troubleshooting
PROFIBUS DPV1 Master
User Manual
Page 179 of 251
ProSoft Technology, Inc.
Processor
Status
Module
Status
PROFIBUS Master
Status
PROFIBUS Master
Status LED Description
CPU is in
Program
mode
PROG
ACTIVE
COM STAT (OFF):
Master is operating but
there are no slaves
responding.
DBASE STAT (GREEN):
PROFIBUS has been
configured.
TKN HOLD (GREEN):
Module is holding the
PROFIBUS token.
MSTR STAT (GREEN):
Master is in operating
mode.
As previously indicated in this User Manual, the module requires the correct
sample program loaded to the processor for correct initialization and operation. If
the sample program is not set up correctly, then the module might not fully
initialize or allow access to the debug menu through PCB.
As indicated below, it is required to have a sample program loaded in the
processor in order to allow debug menu access through PCB and to be able to
reconfigure the MVI56-PDPMV1 module.
Also, if you observe the MSTR STAT LED as RED or blinking GREEN/RED it
means that an incorrect sample ladder logic was loaded to the processor (not
matching the actual module mode (LEGACY or FLEX).
The following tables will help you to troubleshoot different scenarios and the LED
behavior.
4.2.4 Legacy Mode (Use Legacy Mode = Yes)
Scenario
Debug Access After Power Up
LED Behavior After Power Up
- Module located in slot that is not
configured
OR
- No processor
OR
- Neither sample logics loaded to
processor (LEGACY or FLEX)
No
(Waiting for connection to
processor)
MSTR STAT= OFF
COM STAT=OFF
DBASE STAT=GREEN
TKN HLD= OFF
OK = RED
BP ACT = AMBER
APP STATUS= AMBER