MVI56-PDPMV1 ♦ ControlLogix Platform
Diagnostics and Troubleshooting
PROFIBUS DPV1 Master
User Manual
Page 189 of 251
ProSoft Technology, Inc.
Viewing Control Registers
Press
[3]
to view information about the PROFIBUS Master’s Control Registers.
Use this command to view general information about the module, such as the
firmware version and its serial number. The module status contains two possible
codes:
0400 = module is running but not communicating with slaves
0401 = module is running and communicating with slaves
If the module is in STOP mode, the status code is displayed as 0400.
Exiting the Program
Caution:
Some of the commands available to you from this menu are designed for advanced
debugging and system testing only, and can cause the module to stop communicating with the
processor or with other devices, resulting in potential data loss or other failures. Use these
commands only if you fully understand their potential effects, or if you are specifically directed to do
so by ProSoft Technology Technical Support staff.
Some of these command keys are not listed on the menu, but are active nevertheless. Please be
careful when pressing keys so that you do not accidentally execute an unwanted command.
Press
[ESC]
to restart the module and force all drivers to be loaded. The module
will use the configuration stored in the module's flash memory to configure the
module.