PLX51-PBM
Setup
PROFIBUS DPV0/DPV1 Master or Slave to EtherNet/IP™ or Modbus® Gateway
User Manual
ProSoft Technology, Inc.
Page 73 of 196
3.9.6
DPV1 Objects
The DPV1 Objects configuration is shown in the figure below. The slave device
DPV1 Objects configuration window is opened by either double clicking on the slave
device in the tree or right-clicking the slave device and selecting
Configuration
.
Figure 3.92
– Device DPV1 Objects configuration parameters – Logix
Figure 3.93
– Device DPV1 Objects configuration parameters – Modbus
The DPV1 configuration consists of the following parameters:
Table 3.20
– Device DPV1 Objects configuration parameters
Parameter
Description
Slot
The Slot number to which the PROFIBUS DP transaction will be
directed.
Index
The Index number to which the PROFIBUS DP transaction will be
directed.
Size
The size (bytes) of the transaction.
Functions
The Functions supported by the Slave device for this object:
Read
Write
Read/Write
Tagname
The Logix Tagname where the data will be read / written.
(Logix Only)
Modbus Address
The Modbus Holding Register Address where the data will be read /
written.
(Modbus Only)