EtherNet/IP Devices
This tab is enabled when the Primary Interface selected is EtherNet/IP Explicit
Messaging.
IMPORTANT: EtherNet/IP Explicit Messaging is only allowed when the PLX51-PBM is operating as a
Profibus Slave.
The EtherNet/IP Devices configuration is shown in the figure below. Up to 5
EtherNet/IP devices can be configured with up to 50 EtherNet/IP mapped items
allowing for either explicit EtherNet/IP Class 3 or Unconnected Messaging (UCMM)
to any of the 5 configured devices. The data from each EtherNet/IP device is written
to or read from a data table with a size of 10Kbytes. See the
Explicit EtherNet/IP
Messaging Operation
section for more details.
The PLX51-PBM EtherNet/IP Devices configuration window is opened by either
double clicking on the module in the tree or right-clicking the module and selecting
Configuration
.
Figure 3.29
– PLX51-PBM EtherNet/IP Devices configuration
The EtherNet/IP Devices configuration consists of the following parameters:
Table 3.9
– EtherNet/IP Devices configuration parameters
Parameter
Description
EtherNet/IP
Communication
The module can use either
Class 3
or
Unconnected Messaging
when
communicating to the target EtherNet/IP device.
EtherNet/IP Explicit
Timeout
The amount of time with no successful EtherNet/IP responses before the
module sets the EtherNet/IP interface in fault. If
DP Slaves Online during
Communication Failure
has not been set, then all DP slaves being emulated
will go offline on the Profibus DP network.
Scan Class A, B, C,
D
The configurable update rates for each mapped item in the EtherNet/IP Map.
Device List (per device)
Device Name
The user assigned name for the specific device.