PLX51-PBM
Setup
PROFIBUS DPV0/DPV1 Master or Slave to EtherNet/IP™ or Modbus® Gateway
User Manual
ProSoft Technology, Inc.
Page 79 of 196
3.10.2
Generic Module Profile (Logix Pre-V21)
IMPORTANT: When using a Generic Module Profile, the user will need to modify the code generated by
the PLX50CU to match the single connection profile. To do this the user must remove the connection
number from the source and destination tag in the copy blocks (as shown in the example below).
Figure 3.103
– Generated Logix Routine from PLX50CU (highlight connection number)
Figure 3.104
– Modified Logix Routine from PLX50CU for Generic Module Profile
When using Logix versions prior to version 21, then the PLX51-PBM module must be
added to the RSLogix 5000 I/O tree as a generic Ethernet module. This is achieved
by right clicking on the Ethernet Bridge in the RSLogix 5000 and selecting
New
Module
after which the
ETHERNET-MODULE
is selected to be added as shown in
the figure below.
NOTE: See the next section for importing the configuration (L5X).
Figure 3.105 - Add a Generic Ethernet Module in RSLogix 5000
The user must enter the IP address of the PLX51-PBM module that will be used. The
assembly instance and size must also be added for the input, output, and
configuration in the connection parameters section.