PLX51-PBM
Diagnostics
PROFIBUS DPV0/DPV1 Master or Slave to EtherNet/IP™ or Modbus® Gateway
User Manual
ProSoft Technology, Inc.
Page 156 of 196
BF
This LED indicates the status of the PROFIBUS network when in Master mode
and the status of the configured field devices when in Slave Mode.
Master
Solid Red
– There are bus communication errors
Flashing Red
– There are field device errors
Off
– There are no bus communication or device errors
Slave
Solid Red
– There are bus communication errors (if no valid packet has been
received by any configured slave for more than 1s).
Flashing Red
– There are slave errors (at least one slave has not been
configured properly and is not exchanging DPV0 data).
Flashing Green
– All slaves are successfully exchanging DPV0 data and the
DP network operational state is
clear
.
Solid Green
– All slaves are successfully exchanging DPV0 data and the DP
network operational state is
operate
.
Aux
The activity LED is used for the activity on the Primary Interface (e.g.
EtherNet/IP, Modbus RTU, or Modbus TCP). Thus, every time a valid packet is
received from the Primary Interface the LED will toggle green. The LED will
toggle red if a corrupted packet was received (e.g. failed checksum when using
RS232 or RS485).