5.5.6.6 Time
This function allows time and date setting.
5.5.6.7 Language
It is possible to set the national language or English.
5.5.6.8 START Voltage
Start-up voltage can be set according to available photovoltaic system. Voltage
range can be 120V to 350V. Default setting for Aurora is 200V. This parameter
can be changed by means of the display keys.
5.5.6.9 Autotest
Aurora internal test checking correct operation of the protection and the grid
interface device, as provided for by national regulations.
Press ENTER to access all information of this section:
OV = Max. voltage
UV = Min. voltage
OF = Max. Frequency
UF = Min. Frequency
DC injection = Output current direct component. This component shall not be >0.5% with respect to
inverter maximum rated current, or unit will switch off
.
OV test
UV test
OF test
UF test
DC injection
Autotest
Time 14:21
Date 17 May 2006
VStart
200V
English
Italiano