(PVI-6000-OUTD-xx-AU Rev:1.0)
NOTE
: In accordance with the typical assembly diagram (see Fig.9),
each array must be connected to a two-pole DC disconnect switch. An
AC disconnect switch with overload cutout must be used to connect
AURORA to the grid. Recommended ratings for the disconnect switch or
the overload cutout are maximum 40A, 240V.
Fig.9 Wiring diagram
WARNING
: When disconnecting AURORA from the grid, always open
the AC disconnect before the DC disconnect.
AC two-pole
disconnect
switch
Max. Rating
40A/240Vac
PV
Array
2
DC
disconnect
switch
Max. Rating
25A/600Vdc
Grid
Loads
PV
Array
1
DC
disconnect
switch
Max. Rating
25A/600Vdc