The greater the number of panels in each string, the lower the cost and the less
complex the wiring connections of the system.
Fig.2 Array Composition
WARNING
: String voltage shall not exceed 600 Vdc for any reason, so
as to avoid damage to the equipment.
NOTE:
A minimum input voltage of 200 Vdc is required for Aurora to
start the grid connection sequence. Once connected, Aurora will transfer
the maximum power available for any input DC voltage value in a 90V
to 580Vdc range to the grid.