WARNING
: If array current exceeds the maximum capacity of one
inverter input section (18Adc), connect the two sections in parallel by
jumpering the terminals behind the cover (see section 3.7). Jumper wires
should have a 6 sq mm cross-section area (AWG10); connect the
negative wire across terminals –IN1 and –IN2 and the positive wire
across terIN1 and +IN2 as shown in Fig.13. You will also have
to set the inverter for parallel connection (single string) operation by
setting the switch shown in fig. 13 to “PAR”
Fig. 13 Connection/configuration for parallel-connected sections
PAR
Inverter
“parallel”
mode
configuration
Parallel connection of the two
channels