Page 24 of 89
(PVI-6000-OUTD-xx-AU Rev:1.0)
Fig.6 AURORA wall mounting
NOTE:
Ensure Aurora is not exposed to direct sun radiation or other
external heat sources, including the units installed underneath it (see
fig.7). In the event several inverters are stacked up, the heat generated by
the inverters placed at the bottom of the stack could cause ambient
temperature to rise and affect the operation of the inverters in the upper
rows. Temperatures exceeding 40°C could result in a derating of the
output power of the units placed in the upper rows.
A combination of high output power and high ambient temperature will
make the derating problem even worse. For proper cooling, make sure to
install AURORA so as to allow unobstructed air flow (for instance, never
with the front panel facing a solid surface).
Part.A
Part.B