ETHERNET GATEWAY CONFIGURATION
4.6.
Cache Polling Timeout
MODBUS register CACHE_POLLING_TIMEOUT [MODBUS Address:
41502] is used to configure the timeout between two consecutive
pollings of a same cache entry. The Users are free to change this
timeout value at any time. The default polling timeout value is 100ms.
4.7.
Cache Invalidation Timeout
MODBUS register CACHE_INVALIDATION_TIMEOUT [MODBUS
Address: 41503] is used to configure the maximum timeout between
two consecutive MODBUS TCP/IP requests of a cache entry. The
Users are free to change this timeout value at any time. The default
value is 1 second
Note:
The default gateway ID is 254. Please refer to the MODBUS
TCP/IP protocol specification and MODBUS RTU protocol specification
for communication details.
4.8.
Configuration Examples
Example 1:
This example describes the procedure in steps for working with the
dynamic IP address assignation and the Pass-through Mode as an
active operational mode.