Variable Speed Drives of SD700 Series
Connection diagram:
Figure 3.11 SD700
– Ethernet Gateway connector
Once the device is connected, set the following parameters as
follows:
Parameter
Description
Setting
G4.1.1
Main Control Mode
3
The main control of the drive is performed through
communication bus.
G4.1.2
Alternative Control
Mode
3
The alternative control of the drive is performed
through communication bus.
G20.0.1
Communication
Module
0
Modbus; default
G20.1.2
Communication
address
1 – 255 Use different numbers in case of more than 1 inverter
are installed.
G20.1.3
Communication
speed
9600
9600bps.
G20.1.4
Communication parity
ODD
Odd parity