The automatic IP register “ETH_DHCP_ENABLE” [MODBUS
Address: 40922] must be set to “0” to enable static assignment.
Set the required IP address to be assigned to the gateway in the
MODBUS registers [40374], [40375], [40376] and [40377] in
order. For example, if the required IP address to be configured is
192.168.1.145, then write the MODBUS addresses as follows,
[40374] = 192, [40375] = 168, [40376] = 1 and [40377] = 145.
Configure the required MODBUS/RTU communication related
parameters as described in the section „MODBUS RTU
Configuration‟
Set the MODBUS Address [41502] value as “1 – Cache Mode”.
Turn off the gateway
Switch off the jumper for operational mode
Turn on the gateway.
Connect any MODBUS/TCP application with the configured IP
address (192.168.1.145). The gateway will enter into operational
mode.