POWER ELECTRONICS
ETHERNET GATEWAY
ETHERNET GATEWAY CONFIGURATION
37
E
N
G
L
I
S
H
Configure
required
MODBUS/RTU
communication
related
parameters as described in section „MODBUS RTU Configuration‟
Set the MODBUS Addres
s [41502] value as “0 – Pass-through
Mode”.
Turn off the gateway
Switch off the jumper for operational mode
Turn on the gateway. Now the gateway will enter into Operational
Mode.
Connect any MODBUS/TCP application with the assigned IP
address
Establish communication with the MODBUS/RTU slaves by
assigning them required node IDs
In this example nodes with IDs 10 and 21 are connected