3.3.5.
Digital Soft-Starter V5 Series
Connection diagram:
Figure 3.12 V5
– Ethernet Gateway connection
Once the device is connected, set the following parameters as
follows:
Parameter
Description
Setting
G6.1
Control Mode Source
3
Start/Stop-Reset enabled by serial communications.
G14.2
Modbus Device
Address
0 – 240 Use different numbers in case of more than 1 inverter
are installed.
G14.3
Modbus
Communication Baud
Rate
9600
9600bps
G14.4
Modbus
Communication
Parity
NO
Default