3.3.2.
Variable Speed Drives of SD250 Series
Use S+ terminal to connect RS485 high signal and S- terminal to
connect RS485 low signal.
Figure 3.7 TB1 connector of the control board
General specifications:
Transmission form:
Bus method, Multi drop Link System.
Applicable drive:
SD250.
Connectable drives:
Maximum 31.
Transmission distance:
Below 1.200m maximum (700m recommended).
Cable recommended:
0.75mm² (18AWG), Shielded twisted pair.
Installation:
S+ and S- terminals of TB1 connector and CM terminal of TB4
connector located on control board.
Power supply:
Power supply insulated from the inverter power supply.
Specifications of the communication:
Communication speed:
19200 / 9600 / 4800 / 2400 / 1200 bps. Selectable.
Control procedure:
Asynchronous communication system.
Communication system:
Half duplex.
CRC sum check:
2 byte.